Brand Name : GENY
Model Number : YC89S1
Certification : ISO, CE
Place of Origin : CHINA
Payment Terms : L/C,T/T,D/P
Model NO. : YC98S1
Voltage Output : 30V-480V
Current Output : 0.05-10A
LCD Display : With LCD Display
Test Voltage (Full Wave & Fundamental Wave) | |||
Range | 0~500V | ||
Error | ±0.05% (0.1%) | ||
Harmonic | 2nd ~ 51st | ||
Test Current (Full Wave & Fundamental Wave) | |||
Range (direct connection) | 0.025A ~ 12A (Ie=5A) | ||
Range (100AClamp CT) | 0.5~120A (Ie=100A,usage range=0.01Ie~2.4Ie) (Optional: Ie=5A, 500A, 1000A) | ||
Error (direct connection) | ±0.05% (0.1%) | ||
Error (100AClamp CT) | ±0.2%(5A,100A) ±0.5% (other) | ||
Harmonic | 2nd ~ 51st | ||
Starting current | 0.05%Ie | ||
Power Measure Error (Full Wave & Fundamental Wave) | |||
Active Power (Direct connection) | ±0.05% | ||
Active Power (100A ClampCT) | ±0.2%(5A,100A) ±0.5% (other) | ||
Reactive Power (Direct connection) | ±0.1% | ||
Reactive Power (100A ClampCT) | ±0.5%(5A,100A) ±1.0% (other) | ||
Energy Measure Error (Full Wave & Fundamental Wave) | |||
Active Energy (Direct connection) | ±0.05% (±0.1%) | ||
Active Energy (100A ClampCT) | ±0.2%(5A,100A) ±0.5% (other) | ||
Reactive Energy (Direct connection) | ±0.1% | ||
Reactive Energy (100A ClampCT) | ±0.5%(5A,100A) ±1.0% (other) | ||
Error (Harmonic Wave) | |||
Direct Connection | kWh,U, I, P, Q, S | ±0.2%H (H=1+0.01k, k=2~51) | |
Clamp CT 5A/100A | kWh,U, I, P, Q, S | ±0.5%H (H=1+0.01k, k=2~51) | |
Cycle Output Current for 5A CCT’s Self Calibration | 0.05A,0.1A,0.25A,0.5A,1A,2.5A,5A | ||
Error of 5ACCT’s Self Calibration (linear and phase error) | ±0.1% | ||
Clamp CT 500A/1000A | kWh,U, I, P, Q, S | ±1.0%H (H=1+0.01k, k=2~51) | |
Error - Others | |||
Ratio Measurement | ±0.5% | ||
Voltage Influence | <±0.01% | ||
Frequency Influence | <±0.01% | ||
Temperature Influence | <±0.01%/℃ | ||
24h Accuracy Influence | <±0.01% | ||
Harmonic Influence | <±0.01% | ||
Phase angle | |||
Range | -180°~ 180° | ||
Error | <±0.1° | ||
Frequency | |||
Range | 45 ~ 65Hz | ||
Error | ±0.01Hz | ||
Pulse output | |||
Inner High frequency (CH) | Direct connection | 1.8x109 P/kWh | |
Clamp CT | 1.8x109 *(5/Ie)P/kWh | ||
Low frequency output | Direct connection | 3600P, 36000P, 360000P/kWh(kvarh, kVAh) | |
Clamp CT | 3600P, 36000P, 360000P *(5/Ie)P/kWh(kvarh, kVAh) | ||
Pulse ratio | 1:1 | ||
Output level | +5V (can be adjusted according to request) | ||
Pulse input | |||
Input Channel | 2 | ||
Input level | 5 ~ 10V | ||
Max Pulse Input frequency | Max. 10kHz | ||
Display | |||
Resolution | 7’’TFT Touch Screen | ||
System | Windows CE | ||
Other | |||
Voltage supply mode | External power, Tested circuit, Battery | ||
Working power supply | AC 55~600V | ||
Voltage Withstand | 4.0kV (voltage ¤t terminals, power supply & low voltage terminals) | ||
EFT(Electrical Fast Transient) | 2.0kV | ||
IP Level | IP51 | ||
Surge | 2.0kV (common mode), 2.0kV (different mode) | ||
Power on Stability Time | < 3mins | ||
Chargeable battery | 11.1V 3000mAh | ||
Power Consumption | <9W | ||
Operation Temperature | Temperature -20℃ ~ +55℃, humidity 40% ~ 95% | ||
Storage Temperature | Temperature -40℃ ~ +80℃, humidity 40% ~ 95% | ||
Dimension (mm) (W×H×D) | Main | 245×150×50 | |
Carry case | 425×336×196 | ||
Weight (kg) | Main | 2 | |
Whole set | 10 |
1.Multi-Meter Testing:
Tests one or two meters simultaneously, with error display precise to five digits and three decimal places.
2.Automated/Manual Testing:
Automated test sequence for electronic and electromechanical meters.
Manual control via start/stop button or firmware.
3.Data Calculation and Display:
Displays full wave, fundamental wave, harmonic wave data, and U, I, P, Q, VA, phase angle.
Shows positive/negative sequence, zero sequence, and harmonic content.
4.Energy Accuracy Testing:
Tests active/reactive energy for full wave, fundamental wave, and harmonic wave meters.
Tests apparent energy accuracy.
5.Dual-Channel Pulse Testing:
Simultaneous testing of two channels with different pulse constants and modes.
6.Wiring Identification and Energy Accumulation:
Identifies wiring without load.
Measures energy meters without pulse output.
7.Dial Test Function:
Time method or energy method available.
8.Waveform and Vector Display:
Displays vector diagrams and three-phase voltage/current waveforms.
9.Wrong Wiring Identification:
Detects 48 types of three-phase and 96 types of four-wire connections.
Identifies CT secondary crossing wiring.
10.Wiring Simulation and Training:
Simulates wiring scenarios for training and parameter revision without voltage/current signals.
1.Harmonic Analysis:
Calculates harmonic compound of U, I, P, Q, VA and their percentages.
Analyzes up to 51st harmonic (+PH/-PH) and their impact on meter metrology.
2.Full Wave Reactive Power:
Algebraic sum of fundamental and harmonic waves.
Avoids errors from 90-degree phase shift method by selecting harmonic wave numbers based on meter bandwidth.
![]() |